S2000m version 3.0. Security and fire control panel S2000M


Purpose:
is designed for information integration of ISO “Orion” devices in order to organize a single control center and collect system messages, combine alarm loops into sections, create cross connections between sections and outputs of different devices, and expand information display capabilities.
Interaction between the S2000M console and ISO Orion devices occurs via the RS-485 interface with information transmitted in the Orion protocol.

Main characteristics:
Provides display of system messages on a character liquid crystal screen and their storage in a non-volatile buffer (archive) with the ability to view. Controls the display of section states on the “S2000-BI”, “S2000-BKI” and “S2000-BI” display blocks. 01. For better perception of messages, it is possible to specify text descriptions of sections, alarm loops, addressable detectors and users.
Allows you to manage sections (arm and disarm) using a PIN code on the remote control itself or on the S2000-K and S2000-KS keyboards, Touch Memory keys or Proximity cards from any device that has an input for connecting a reader , from S2000-BKI units, SMS messages via UO-4S.
Allows you to remotely control the S2000-ASPT and Potok-3N devices using commands from the remote control and from the S2000-PT display units: select automatic or manual control mode for fire extinguishing installations, initiate their launch and cancel the launch. Controls the display of the states of fire extinguishing zones on the “S2000-PT” and the states of the water fire extinguishing installation on the “S2000-BI” version. 01.
Provides differentiation of user access rights to management functions.
Has a function automatic control outputs of control panels, starting and relay units according to 45 different programs.
Supports output control scenarios, voice notification, alarm loops and access modes. Output control scenarios allow you to create your own programs for controlling actuators. Scenarios for controlling voice notification allow you to control voice notification devices of the "High-horn" series and can be used for synchronous notification and with the division of an object into zones. Access mode control scripts are designed to automatically open doors along escape routes in case of fire. Loop control scenarios can be used to automatically control alarm loops (for arming or disarming) or operating modes of the S2000-ASPT and Potok-3N devices based on system events.
Supports connection to Orion workstation or Orion Pro workstation to increase functionality and system expansion.
It has the ability to connect a printer with a serial RS-232 interface for documenting events or a PC with AWP “S2000” software for displaying events, states of sections and alarm loops.
Ensures the transmission of notifications by the S2000-IT, UO-4S, UO-Orion and S2000-PP devices. It has the ability to connect the ATS100 radio transmitter of the LARS security radio system or the RS-202TD radio transmitter of the “Reef String 202” (“LONTA 202”) security radio system for transmitting notifications over the radio channel.
Configuring the console in the “Pprog.exe” program or in the program module Database Administrator of the Orion Pro automated workplace.

Buy Bolide S2000M from Layta at an attractive price. Car S2000M: description, characteristics, customer reviews, photographs and related products..

    The following features have been added:
  • Added a new "duress code" password attribute. When an object is controlled by the enforcement code, it is converted to anxiety"Compulsion". Duress is displayed as an alarm condition when the ATTACK state's alarm setting is set to ALARM WITH SOUND or ALARM WITHOUT SOUND, and is hidden when the setting is set to NON ALARM. When a partition is disarmed using the duress code, the “DURES DISARMED” event is generated. The “Dussion code presented” event is supported, which sets the “Derress” alarm state for the “reader” object (intended to generate an alarm when accessing the ACS using a duress code). This alarm is reset by the manual command "Reset alarms". The Duress state controls outputs with programs 54 “Turn on during attack” and 55 “Turn off during attack” (“Attack” includes the states “Derusion” and “Silent alarm”).
  • Added control function for one touch of the TM key/card to the reader. To do this, access levels now have the “Control Style” attribute, which takes two values: 1) “Display state, then manage”; 2) "Manage immediately." If the control style is set to “Manage immediately”, then when you bring a key with partition management rights to the reader, the partition is immediately managed. This management style is suitable for users with management rights to one partition.
  • Added alarm settings for events:
    • "Assault" (includes "Coercion" and "Silent Alarm");
    • "Entry alarm".
  • Added relay control programs:
    • 54 "Enable during attack";
    • 55 "Turn off when attacked";
    • 56 "Lamp 2";
    • 57 "Siren 2".
    The programs "Lamp 2", "Siren 2" are intended for radio annunciators with autonomous power supply. A setting has been added that allows you to control relays with programs 1 – 8 with a delay during “Fire 2” (as in “S2000M” version 2.07).
    Changes to existing features:
  • For ease of use of the S2000M, the user interface of the main operating mode has been redesigned:
    • The number of required actions to view alarms, fires, starts, and faults has been reduced. The display of the number of sections with alarms, fires, starts, and malfunctions has been changed;
    • the proposed control commands better correspond to the state of the partition and its type (for example, for a security partition in an alarm, a disarming command is proposed);
    • events displayed on the screen in standby mode do not interfere with entering the password using the numeric buttons.
  • Added display of the number of sections containing actuators that are blocked or in manual control mode (automation is disabled), added viewing of sections with automation states “Blocking” and “Manual control” (“Automation is disabled”). A filter has been added to the event log by event type "Blocking";
  • Setting up event broadcasting for the “S2000 Remote Control” object in the PProg program now only affects the operational display of ongoing events on the screen, and all events are available in the log. This makes it possible to disable the live display of events. When the event display is turned off, the indication of the object’s state - the presence of alarms, fires, starts, shutdowns, faults and shutdowns - is retained.
  • The user number has been added to the “Partition armed” and “Partition disarmed” events, if a partition (group of partitions) is armed or disarmed not entirely by the partition control command, but in parts. Examples:
    • a section (group) was armed (disarmed) as a result of local control of the loops of this section (arming or disarming with keys recorded in the “S2000-4”, “Signal-10” receiving and control unit);
    • a group of partitions was armed (disarmed) as a result of arming (disarming) the partitions of the group. The “Partition removed” event has also been generated when it is disabled. These changes are useful when using notification transmission in Ademco protocols Contact ID or LARS.
  • Two parameters have been added to the LARS protocol settings: which user number to transmit in the “partition taken” and “partition removed” events if the user number is unknown, and which user number to transmit if the user number in the event exceeds the maximum possible meaning. The default settings of these parameters correspond to the operating tactics of "S2000M" version 2.06: the events "partition taken" and "partition removed" are not transmitted if the user is unknown, and events with a user number that is too large are transmitted with the maximum allowable user number. The operation tactics of "S2000M" version 2.07 can be obtained if you set "1" as the number for the unknown user.
  • The names of the events have been changed: “WATER LEAKAGE” to “FLOODING”, “NO WATER LEAKAGE” to “DZ RESTORATION”, “OVERGR.RIP DEVICE” to “CURRENT IS NORMAL”.
    Bugs fixed:
  • It was possible for a one-time false activation of the relay after configuration by the PProg program if the relay control programs were changed.
  • Fixed a bug in the "input loops" function. The conflict of “input loops” configured simultaneously in the “S2000M” and the receiving and control unit has been eliminated (with simultaneous configuration, the “input loops” will work according to the settings of the receiving and control unit).
  • The event with the result of the operation was not displayed when directly controlling the device's AL (password with access level 253 - 255).
  • The "Partition Armed" event was not generated if the partition was armed with a key with alarm control rights (a key recorded in the "S2000-4" or "Signal-10" receiving and control unit), and the partition had an alarm zone with arming delay on guard. The messages “Partition taken” / “Partition removed” might not be generated if some of the partition inputs were set / removed by alarm loop control scripts.
  • If the user first selected an action with the "RESET", "START", "STOP" key or pressed the context menu key, then identified himself (entered a password) and then exited viewing sections with the " ×", the message "Invalid partition" might be displayed.
  • There may have been no initial indication of the status of actuators (outputs type " technological equipment") to "S2000-BI/BKI" after exiting "S2000M" from the programming mode until the state of the actuators changes.
  • The transfer of control requests from "S2000-K" and "S2000-KS" to the "Orion Pro" workstation did not work when the "CENTRAL CONTROL" parameter was enabled.
    Compatibility Details:
  • Configuration with the program "Pprog.exe" version 3.03 build 1 or higher.

The remote control is designed to work as part of an addressable security system fire alarm and management fire fighting equipment. Together with ISO "Orion" devices, it can perform the functions of a block-modular security and fire alarm control device, a control device for light, sound and voice warning, gas, powder aerosol and water fire extinguishing, smoke protection, engineering systems. Information interaction between blocks is carried out via a wired communication line RS-485

Remote control "S2000M" version 3.00 has been modified for use in fire alarm and control systems fire protection in accordance with the requirements of GOST R 53325-2012. Changes affected the design and software device.

Design changes:

  • Single light indicators have been changed. The new "S2000M" has red indicators for the presence of fire alarms and running fire protection equipment, yellow indicators for turning off the internal audio signal, the presence of faults, disconnected elements, stopped fire protection equipment, and a green indicator for the presence of power;
  • The functions of the buttons and the labels on the buttons have been changed:
    • dedicated keys have been added to turn off the sound signal, reset alarms, manually start and stop fire protection equipment (alerts);
    • Dedicated keys for arming, disarming, and entering the programming menu have been removed;
  • the event log memory has been increased (8000 events) and the control script memory has been increased (6 times compared to version 2.07);
  • two power inputs (main and backup) with voltage control on both inputs;
  • non-volatile real time clock.

New features:

  • The indication of the device state in the "Fire", "Alarm", "Start" (starting fire protection equipment), "Fault" modes has been changed: the device displays the zone (section) in the "Fire" (or "Start" or "Alarm" state "), the number of zones (partitions) in the states "Fire", "Start", "Alarm", "Stop", "Fault", "Disabled", allows you to view zones (partitions) in these states and individual elements(alarm loops, detectors, outputs);
  • a function has been introduced to disable controlled inputs (alarm loops, addressable detectors) and outputs (those controlled by the S2000M), which allows you to quickly, without changing the configuration of the S2000M, exclude them from security and control;
  • a function has been introduced for manual control of the start and stop of fire protection equipment and other actuators activated by relay outputs controlled by the S2000M. Manual starting and stopping of devices is possible from the S2000M controls, the S2000-PT and S2000-BKI display units, and using the EDU 513-3AM remote start devices. Events and states have been introduced to display the startup of devices used for fire protection;
  • Functions have been introduced for displaying the fire extinguishing start delay on the "S2000M" indicator and "S2000-PT" blocks of versions from 2.50 and higher, suspending the delay count and resetting it (start without delay). These functions are available when using "S2000-ASPT" versions 3.50 and higher;
  • added the ability to work with a computer (with AWS programs "Orion Pro", PProg) at speeds of 38400, 57600 and 115200 bps.
Note

"S2000M" versions 2.xx cannot be updated to version 3.00.

Remote controller "S2000M" version 3.00 modified for use in fire alarm systems and control of fire protection equipment in accordance with the requirements GOST R 53325-2012. The changes affected the design and software of the device.

Design changes:
  • Single light indicators have been changed. The new "S2000M" has red indicators for the presence of fire alarms and running fire protection equipment, yellow indicators for turning off the internal audio signal, the presence of faults, disconnected elements, stopped fire protection equipment, and a green indicator for the presence of power;
  • The functions of the buttons and the labels on the buttons have been changed:
    • dedicated keys have been added to turn off the sound signal, reset alarms, manually start and stop fire protection equipment (alerts);
    • Dedicated keys for arming, disarming, and entering the programming menu have been removed;
  • the event log memory has been increased (8000 events) and the control script memory has been increased (6 times compared to version 2.07);
  • two power inputs (main and backup) with voltage control on both inputs;
  • non-volatile real time clock.
New features:
  • The indication of the device state in the "Fire", "Alarm", "Start" (starting fire protection equipment), "Fault" modes has been changed: the device displays the zone (section) in the "Fire" (or "Start" or "Alarm" state "), the number of zones (partitions) in the states "Fire", "Start", "Alarm", "Stop", "Fault", "Disabled", allows you to view the zones (partitions) and individual elements located in these states ( alarm loops, detectors, outputs);
  • a function has been introduced to disable controlled inputs (alarm loops, addressable detectors) and outputs (those controlled by the S2000M), which allows you to quickly, without changing the configuration of the S2000M, exclude them from security and control;
  • a function has been introduced for manual control of the start and stop of fire protection equipment and other actuators activated by relay outputs controlled by the S2000M. Manual starting and stopping of devices is possible from the S2000M controls, the S2000-PT and S2000-BKI display units, and using the EDU 513-3AM remote start devices. Events and states have been introduced to display the startup of devices used for fire protection;
  • Functions have been introduced for displaying the fire extinguishing start delay on the "S2000M" indicator and "S2000-PT" blocks of versions from 2.50 and higher, suspending the delay count and resetting it (start without delay). These functions are available when using "S2000-ASPT" versions 3.50 and higher;
  • added the ability to work with a computer (with AWS programs "Orion Pro", PProg) at speeds of 38400, 57600 and 115200 bps.
"S2000M" versions 2.xx cannot be updated to version 3.00.

Detailed information about "S2000M" version 3.00 is given

Editor's Choice
Your Zodiac sign makes up only 50% of your personality. The remaining 50% cannot be known by reading general horoscopes. You need to create an individual...

Description of the white mulberry plant. Composition and calorie content of berries, beneficial properties and expected harm. Delicious recipes and uses...

Like most of his colleagues, Soviet children's writers and poets, Samuil Marshak did not immediately begin writing for children. He was born in 1887...

Breathing exercises using the Strelnikova method help cope with attacks of high blood pressure. Correct execution of exercises -...
About the university Bryansk State University named after academician I.G. Petrovsky is the largest university in the region, with more than 14...
Representatives of the arachnid class are creatures that have lived next to humans for many centuries. But this time it turned out...
Why do you dream of wedding shoes? Why do you dream of wedding shoes with heels?